HV Diagnostics TD30 30kV Tan Delta Bridge
$7.350
The TD30 was the first small portable VLF TD system with wireless Bluetooth technology that really made performing Tan Delta testing in the field easy to perform. Compared to other TD systems on the market that required several connections to be made or were large and bulky, the TD30 requires very few connections and does not use any special batteries or fiber optic cabling that is prone to damage in the field environment.
Description
HV DIAGNOSTICS TD30 30KV TAN DELTA BRIDGE
The HV Diagnostics TD30 30kV Tan Delta Bridge is an easy to use, single piece, Digital Signal Processor based, field portable, fully automatic VLF (Very Low Frequency) high voltage measurement instrument developed for the high potential measuring of the insulation dielectrics of various types of electrical apparatus.
features:
- 0-30kV tan delta bridge
- Compact and battery operated
- Solid state, air insulated design
- Configuration and data extraction through Bluetooth connection • Supplied with complete analysis software
- Real time display of actual output waveform
- Suitable for use with HV Diagnostics HVA30 VLF system
This item is part of our rental fleet and will show signs of normal wear due to use. It has been regularly tested, maintained, and cleaned upon each rental return. Stock images are used on the website for listing purposes.
Technical Specifications
Ordering Information:
• 700 003
Power Supply:
• 2 C Type Batteries
Rated Operating Voltage:
• RMS
1-23kV
• Peak
33kV
Voltage Measurement:
• Resolution
0.1kV
• Accuracy
1% (of reading)
Current: Measurement
• Resolution
1µA
• Accuracy
1% (of reading)
Frequency Measurement
• Range
0.01 to 0.1Hz
• Resolution
0.01Hz
Tan Delta / Dissipation Factor Measurement:
• Resolution
1 x 10
-5
• Accuracy >15nF
±1 x 10
-4
• Accuracy <15nF
±3 x 10
-4
• Minimum Load:
5nF
Weight:
• 7 lbs / 3 kgs
Dimensions:
• (Length x Diameter) 9.5 x 3.5 inches / 240 x 85mm
Computer Interface:
• Bluetooth
Accessories Included:
• Integrated HV and Grounding Cable
• Bluetooth USB Dongle
• TD Control Center Software
• Operating Manual
• Corona Protection
Standards:
• Shock
• IEC68-2-27
• Vibration
• IEC68-2-6
• EMC
• IEC6100-4-2, IEC6100-4-4, EN55011
• Safety
• EN60950, EN50191, EN61010-1
Environmental:
• Storage
-13°F to 158°F / -25°C to 70°C
• Operating
23°F to 113°F / -5°C to +45°C
• Humidity
80% RH non-condensing
Reviews
There are no reviews yet.